Eagle Eye GD-3000 Combustible Gas Detector / Controller / Transducer
Alpine Power Systems' experienced technical support & sales team is here to assist your needs:
The Eagle Eye GD-3000 combustible gas detector is a versatile, easy-to-use device that allows you to select between methane (NG), propane (LP), or hydrogen (H2) gas detection.
On this page:
The Eagle Eye GD-3000 combustible gas detector is a versatile, easy-to-use device that allows you to select between methane (NG), propane (LP), or hydrogen (H2) gas detection. The GD-3000 provides low-level detection of combustible gas in an easy-to-maintain monitor that is factory calibrated for simple installation. This low voltage gas detector provides automatic feedback and fan control that can help reduce combustible gas concentrations in battery rooms, parking garages, maintenance facilities, and other locations that require combustible gas detection. The unit can be used with 12VDC or 24VDC N.O. (fire/security) panels.
The GD-3000 Includes:
GD-3000 Unit
User Manual
*4 x 4 electric mounting box is not included
The GD-3000 Methane, Propane, or Hydrogen combustible gas detector does not require any regular maintenance or service other than cleaning. The unit uses a long life pellistor sensor that has over a five-year life expectancy. The unit is factory calibrated, but can also be field-calibrated. Calibration kits include Methane, Propane or Hydrogen gas, a gas regulator with two feet of plastic tubing, humidifier and gas test hood.Eagle Eye GD-3000 Advantages:
Selectable (on/off) digital display, audible alarm buzzer, fan relay (minutes), fan minimum run time
Selectable fan and alarm relay activation
Factory Calibrated - Can also be field calibrated using 10% LEL Methane, 10% LEL Propane or 10% LEL Hydrogen gas regulator and calibration hood
One screw allows access for easy calibration
Mounts on a standard 4" x 4" electrical box, no cover needed
5 A SPDT fan relay controls starters of exhaust fans
0.5 A.N.O. or N.C. alarm relay connects to warning devices or control panels
Supervised system design: internal detector problem will cause the fan & alarm relay to activate
ETL Listed to UL 61010-1
GD-3000 can be used with 12VDC or 24VDC N.O. (fire) panels
Alarm panel provides battery back-up power to GD-3000
GD-3000 dry contact fan relay can use panel power or fan power
Match fan relay contacts to fan size, and coil voltage to power source
Alarm control panels are available with many features and can control other devices such as smoke detectors, fire detectors and burglar alarms
Eagle Eye GD-3000 Applications:
Utilities and Power Plants
UPS Power Systems
Fuel Cell Test Stations
Nuclear Waste Reforming
Diesel and other IC Engines
Construction and Maintenance Facilities
Medical/Biotechnology Labs
Hydrogen Refueling Stations
Fire Department
Battery Suppliers
Motive Power
Eagle Eye GD-3000 FAQs:
What is the lifespan of the GD-3000 sensor?
The sensor has a 5-year active lifespan; after this time the end-of-life signal will cause an error code t200 “Sensor expired”. In this error mode, the Alarm relay will be activated, the 4-20 mA current loop will go to 24 mA, the unit will display the error code, the green status indicator LED light will flash and the buzzer will chirp intermittently. The Fan relay will also engage if the Trouble Fan Setting Option is set to “ON”. The Fan relay will not engage if the Trouble Fan Setting Option is set to “OFF”.
Am I able to calibrate the sensor at its end of life?
Five (5) years after the GD-3000 is installed the sensor end-of-life signal will be activated indicating that the GD-3000 has reached the end of its typical usable life. The sensor life can be reset for 1 year. Max life is 6 years from initial install, then permanent EOL error will occur and the unit will need replaced.
What gases will the GD-3000 sense?
The GD-3000 combustible gas detector allows you to select between methane, propane or hydrogen gas detection. The default gas setting is ME (methane). For other flammable gases, one can speculate on the anticipated sensitivity of the sensor alone, but since the relative sensitivities to various gases is also dependent on the mounting arrangement within an environment and other factors, it is always recommended that the instrument user determines the response of the sensor to the target gas by experiment using the final product wherever possible.
Where should I mount the GD-3000 Gas Detector?
This would depend on several factors including the area size, gases detecting, ventilation locations, et cetera. Our advice is to mount the unit as close as possible to the equipment it will be protecting/monitoring and then conducting experimental testing. If the target gas is heavier than air; propane (LP), mount the GD low on a wall or column (about one foot above the floor) in a central area where air movement is generally good, if it is lighter than air mount the unit high on the wall or ceiling.
How is the GD-3000 powered?
The GD requires 3 W (max) from either 12 – 24 VAC or 12 – 48 VDC sources.
Manufacturer
See below for documentation relating to this product line that is available to download. To download this documentation, please click on the desired document you’d like to download and fill out the required form information fields. You will be able to view and download the documents upon completion of the download form.