10 year Design Life @ 25°C
Absorbent Glass Mat (AGM) technology for efficient gas recombination of over 99%
Patented Long Life Alloy having the lowest calcium levels in the industry minimizing grid growth, reducing gassing, and extending battery life
Flame arresting, one-way pressure-relief vent for safety and long life
UL Recognized Component
Flame retardant polypropylene case and covers
Thermally welded case-to-cover bond to eliminate leakage
Not restricted for air/surface/water transport
C&D Ohmic Ring for ease of maintenance readings on TFA models
C&D UPS High Rate Max Front Access Specifications:
Operating Temperature Range (With Temp. Compensation:
Discharge: -40°F (-40°C) to +160°F (71°C)
Charge: -10°F (-23°C) to +140°F (60°C)
Nominal Operating Temperature Range: +74°F (23°C) to +80°F (27°C)
Float Charging Voltage:Â 13.5 to 13.8 VDC average per 12V unit
Equalize Charge & Cycle Service Voltage: 14.40 to 14.80 VDC average per 12V unit @ 77°F (25°C)
Self-Discharge: Battery can be stored up to 6 months at 77°F (25°C) before a freshening charge is required. Batteries stored at temperatures greater than 77°F (25°C) will require recharge sooner than batteries stored at lower temperatures.
High Rate Max Front Access Batteries are the perfect fit for UPS applications including:
Data Centers
Network Operations Centers
Industrial Process Control Facilities
Internet Housing Sites
Semiconductor Manufacture
Banks & Financial Markets
Applications
- Security & Alarms
- Data Center
- UPS
Technologies
- AGM (VRLA)
Manufacturer
See below for documentation relating to this product line that is available to download. To download this documentation, please click on the desired document you’d like to download and fill out the required form information fields. You will be able to view and download the documents upon completion of the download form.
Find C&D High Rate Max Front Access Batteries in the following product categories:
Manufacturer