The EnerSys PowerSafe® DDm DDm125-27 battery range offers an ideal solution for large capacity Valve Regulated Lead-Acid (VRLA) battery requirements. EnerSys PowerSafe® DDm DDm125-27 battery’s steel can (module) design, with its integral racking system, provides a cost effective battery system. This creates a compact, quick and simple installation process. EnerSys PowerSafe® DDm DDm125-27 battery, with its optimized recombination technology and extra thick plates, provides excellent performance and service life across a wide range of applications including: telecommunications, power generation/distribution sites, and UPS.
General Specifications:
Nominal Capacity (Ah):
10hr. rate 1.80Vpc @ 20°C: 1625
8hr. rate 1.75Vpc @ 77°F: 1625
Nominal Dimensions:
Length (mm): 271
Length (in): 10.7
Height (mm): 226
Height (in): 8.9
Can Depth (mm): 526
Can Depth (in): 22.1
Module Depth (mm): 597
Module Depth (in): 23.5
Typical Weight of Cell(s) in Can (kg): 120.8
Typical Weight of Cell(s) in Can (lbs): 268.4
Internal Resistance Micro-Ohms: 155
Short Circuit Current (Amps): 13452
Electrolyte (1.300 S.G.)
Volume (per cell) (oz): 691
Volume (per cell) (L): 20.3
Weight (per cell) (lbs): 58.2
Weight (per cell) (kg): 26.4
Pure Acid (1.835 S.G.)
Volume (per cell) (oz): 193.0
Volume (per cell) (L): 5.7
Weight (per cell) (lbs): 23.0
Weight (per cell) (kg): 10.4
Lead Weight (per cell) (lbs): 178
Lead Weight (per cell) (kg): 80.7