Deka Unigy I 12AVR145ET sealed lead-acid batteries are available as AVR (absorbed valve regulated) and GVR (gel valve regulated) technology for virtually any application demand. Both are UL recognized components and are made in the U.S.A. with individually tank-formed plates for optimized uniformity of cell-to-cell voltages.
Deka Unigy I 12AVR145ET General Specifications:
Nominal Voltage: 12-Volt/145 ampere-hours @ 8hr rate to 1.75 final volts/cell
Positive Plate: Pure lead, low-calcium, high-tin alloy
Negative Plate: Lead calcium alloy
Post Seal: Epoxy-sealed
Terminal: Front access, 1/4" x 20 brass insert
Container: Flame-retardant, polypropylene - UL94 V0/>28% L.O.I.
Safety Vent: Low positive pressure, self-sealing w/ flame arrestor
Float Voltage: 2.25 volts per cell +/- 0.01 vpc (Range: 13.44 to 13.56 volts per 6-cell unit)
Battery Life: 10 years in float applications at 77ºF/25°C
Length: 446.6 mm, 17.58 in
Width: 174.9 mm, 6.89 in
Height: 256.5 mm, 10.10 in
Weight: 47.7 kg, 105 lbs
|