Deka Unigy I 12AVR-150ET Batteries
Deka Unigy I 12AVR-150ET sealed lead-acid batteries are available as AVR (absorbed valve regulated) and GVR (gel valve regulated) technology for virtually any application demand. Both are UL recognized components and are made in the U.S.A. with individually tank-formed plates for optimized uniformity of cell-to-cell voltages.
Deka Unigy I 12AVR-150ET General Specifications:
Nominal Voltage: 12-Volt/150 ampere-hours @ 8hr rate to 1.75 final volts/cell
Positive Plate: Pure lead, low-calcium, high-tin alloy
Negative Plate: Lead calcium alloy
Post Seal: Epoxy-sealed
Terminal: Front access, 1/4" x 20 brass insert
Container: Flame-retardant, polypropylene - UL94 V0/>28% L.O.I.
Safety Vent: Low positive pressure, self-sealing w/ flame arrestor
Float Voltage: 2.25 volts per cell +/- 0.01 vpc (Range: 13.44 to 13.56 volts per 6-cell unit)
Battery Life: 10 years in float applications at 77ºF/25°C
Length: 558.8 mm, 22.00 in
Width: 124.5 mm, 4.90 in
Height: 298.5 mm, 11.75 in
Weight: 52.2 kg, 115 lbs
Downloads & Documentation
See below for documentation relating to this product line that is available to download. To download this documentation, please click on the desired document you’d like to download and fill out the required form information fields. You will be able to view and download the documents upon completion of the download form.
- Deka Unigy 1 Telco Rack Systems Flyer
- Deka Unigy 1 Telecom Solutions Flyer
- Deka-Unigy-12AVR75100-Flyer.pdf
- Deka Unigy 1 IO Manual
- Deka Unigy 12AVR130
- Deka Unigy 12AVR145ET
- Deka Unigy 12AVR145L & 145LLP Flyer
- Deka Unigy 12AVR150ET
- Deka Unigy 12AVR170ET
- Deka Unigy 12AVR200ET
- Deka Unigy 12AVR30-12AVR40
- Deka Unigy 12AVR75-12AVR100
- Deka Unigy 12AVR90
- Deka Unigy 12AVR ET100