EnerSys® PowerSafe® OGi batteries feature Vented Lead Acid (VLA) technology ideal for utility market applications.

EnerSys PowerSafe OGi Batteries

On this page:

EnerSys® PowerSafe® OGi batteries feature Vented Lead Acid (VLA) technology ideal for utility market applications. OGi’s rod plate composition offers a high energy density design providing a space-efficient footprint savings and long life. The low antimony alloy grid reduces water consumption and subsequently reduces maintenance costs.

The high impact molded clear Styrene Acrylonitrile (SAN) jar allows for easy inspection of the plates and electrolyte level. The elevated post design allows easy access for utilizing measuring devices to ensure fast and easy voltage and ohmic readings for fulfillment of NERC requirements.

High integrity terminal design maximizes operational safety and inhibits electrolyte leaks. These features along with insulated copper connectors provide a reliable, safe and durable battery for your utility applications.

Features and Benefits

  • Proven, reliable flooded lead acid battery technology

  • Excellent for utility duty cycle

  • Industry-standard size jars

  • Amp-hour range 60Ah to 280Ah (C8 to 1.75Vpc @ 77°F)

  • Space saving footprint design in 12V and 6V configurations

  • Fully insulated connectors for personal protection

  • Raised terminal posts to enable measurements directly from post

Construction

  • Rod style positive flat plate grid

  • Pasted flat plate negative grid optimized for maximum performance

  • Special microporous separator with glass fiber mat

  • Durable, high impact resistant, clear SAN jar allows visual inspection of plates and electrolyte

  • Opaque ABS (Acrylonitrile Butadiene Styrene) lid

  • Dilute sulphuric acid electrolyte - 1.240 Specific Gravity at maximum level line

  • Leak resistant safety pole post design with brass insert

Installation and Operation

  • Footprint offers extremely efficient space utilization

  • Equipped with flame arrestor vent plugs for safe operation

  • Encapsulated connectors and bolts offer added safety

  • Raised posts allow easy parameter measurements without disassembly

  • Low antimony grid alloy greatly reduces watering intervals compared to antimony grid

  • Operating temperature range: 14°F (-10°C) to 113°F (45°C) Recommended temperature range: 68°F (20°C) to 86°F (30°C)

Standards

  • Compliant with IEC 60896-11

  • Compliant with DIN 40737-3

Alpine Power Systems is a platinum value-added reseller of EnerSys Battery products. Alpine can provide battery services on all EnerSys batteries including engineering, installation, preventative maintenance, monitoring and recycling. Contact us today for pricing and technical inquiries.

Technologies

  • Lead Acid - Flooded

Manufacturer

EnerSys

EnerSys

See below for documentation relating to this product line that is available to download. To download this documentation, please click on the desired document you’d like to download and fill out the required form information fields. You will be able to view and download the documents upon completion of the download form.

PDF Document
enersys-powersafe-flooded-instruction-manual.pdf
PDF Document
enersys-powersafe-ogi-battery-performance-specs.pdf
PDF Document
enersys-powersafe-ogi-battery-range-summary.pdf

ISO Certifications

Alpine Power Systems is proud to have three ISO Certifications that have been awarded to us after comprehensive audits completed by third-party, independent experts. Alpine must validate that all ISO processes are being followed through yearly follow up inspections.

Certification Certification Certification

Contact Us

Alpine Power Systems' experienced technical support & sales team are here to assist your needs.